RCC MEMBER DESIGN
TIPS
A.BEAMS:
OVERALL
DEPTH OF BEAMS:
| 
SL.NO | 
MEMBER | 
SPAN/OVERALL DEPTH RATIO | 
| 
1. | 
PLINTH BEAM | 
15 TO 18 | 
| 
2. | 
TIE BEAM | 
18 TO 20 | 
| 
3. | 
FLOOR BEAMS | 
12 TO 15 | 
| 
4. | 
GRID BEAMS | 
20 TO 30 | 
 1. Beam sections should be designed for:
- Moment values at the column face
     & (not the value at center line as per analysis)
- Shear values at distance of
     d  from the column face. (not the
     value at center line as per analysis)
- Moment redistribution is allowed
     for static loads only.
- For beams spanning between the
     columns about the weak axis, the moments at the end support shall be
     reduced more and distributed and the span moments shall be increased
     accordingly to account for the above reduction. 
- Moment distribution shall be
     done in such a way that 15% of the support moments shall be added to the
     span moment without the support moments getting reduced. 
- The section within the span
     shall be designed for the increased span moment which will account for the
     concentrated & isolated loading that may act within one span.
- Moment redistribution is not
     allowed if
- moment co-efficient taken from
      code table
- designed for earthquake forces
      and for lateral loads.
- At least 1/3 of the +ve moment
     reinforcement in SIMPLE SUPPORTS & ¼ the +ve moment reinforcement in
     CONTINUOUS MEMBERS shall extend along the same face of the member into the
     support, to a length equal to Ld/3. (Ld-development length)
- Use higher grade of concrete if
     most of the beams are doubly reinforced. Also when Mu/bd^2 goes above 6.0.
- Try to design a minimum width
     for beams so that the all beam reinforcement passes through the columns.
     This is for the reason that any reinforcement outside the column will be
     ineffective in resisting compression.
- Restrict the spacing of stirrups
     to 8”(200mm) or ¾ of effective depth whichever is less.(for static loads)
- Whenever possible try to use
     T-beam or L-beam concept so as to avoid compression reinforcement.
- Use a min. of 0.2% for
     compression reinforcement to aid in controlling the deflection, creep and
     other long term deflections.
- Bars of Secondary beam shall
     rest on the bars of the Primary beam if the beams are of the same depth.
     The kinking of bars shall be shown clearly on the drawing.
- Length of curtailment shall be
     checked with the required development length.
- Keep the higher diameter bars
     away from the N.A(i.e. layer nearest to the tension face) so that max.
     lever arm will be available.
- Hanger bars shall be provided on
     the main beam whenever heavy secondary beam rests on the main beam.(Try to
     avoid the hanger bar if secondary beam has less depth than the main beam,
     as there are enough cushions available).
- The detailing for the secondary
     beam shall be done so that it does not induce any TORSION on the main
     beam.
-  For cantilever beams reinforcement at the
     support shall be given a little more and the development length shall be
     given 25% more.
- As a short cut, bending moment
     for a beam (partially continuous or fully continuous) can be assumed as
     wl^2/10 and the same reinforcement can be detailed at span and support.
     This thumb rule should not be applied for simply supported beams.
B:SLAB
          EFFECTIVE DEPTH:           
| 
Sl.no | 
SLAB | 
SPAN/EFFE.DEPTH | 
| 
1. | 
One- way simply supported slab | 
30 | 
| 
2. | 
One-way continuous slabs | 
35 | 
| 
3. | 
Two-way simply supported slabs | 
38 for L/B=1.5 
35 for
  L/B>1.5 | 
| 
4. | 
Teo-way continuous slabs | 
40 for L/B=1.5 
38 for
  L/B>1.5 | 
- Whenever the slab thickness is
     150mm, the bar diameter shall be 10mm for normal spacing.(It can be 8mm at
     very closely spaced).
- Slab thickness can be
     100mm,110mm,120mm,125mm,150mm, etc.
- The maximum spacing of Main bar
     shall not exceed 200mm(8”) and the distribution bars @ 250mm(10”).
- If the roof slab is supported by
     load bearing wall(without any frames) a bed block of 150/200mm shall be
     provided along the length of supports which will aid in resisting the
     lateral forces.
- If the roof is of sheet(AC/GI)
     supported by load bearing wall (without any frames) a bed block of
     150/200mm shall be provided along the length of supports except at the
     eaves. The bed block is provided to keep the sheets in position from WIND.
     
- For the roof slab provide a min.
     of 0.24%  of slab cross sectional
     area reinforcement to take care of the temperature and other weathering
     agent and for the ponding of rain water etc since it is exposed to outside
     the building enclosure.
COLUMN:
- Section should be designed for
     the column moment values at the beam face.
- Use higher grade of concrete
     when the axial load is predominant.
- Go for a higher section
     properties when the moment is predominant.
- Restrict the maximum % of reinforcement
     to 3.
- Detail the reinforcement in
     column in such a way that it gets maximum lever arm for the axis about
     which the column moment acts.
- Position of lap shall be clearly
     mentioned in the drawing according to the change in reinforcement.
     Whenever there is a change in reinforcement at a junction, lap shall be
     provided to that side of the junction where the reinforcement is less. 
- Provide laps at mid height of
     column to minimize the damage due to moments(Seismic forces).
- Avoid KICKER concrete to fix column
     form work since it is the weakest link due to weak and non compacted part.
FOOTING:
- Never assume the soil bearing
     capacity and at least have one trial pit to get the real site Bearing
     capacity value.
- Check the Factor of Safety used
     by the Geo technical engineer for finding the SBC.
- SBC can be increased depending
     on the N-value and type of footing that is going to be designed. Vide
     IS-1893-2000(part-I).
- Provide always PLINTH BEAMS
     resting on natural  ground  in orthogonal directions connecting all
     columns which will help in many respect like reducing the differential
     settlement of foundations, reducing the moments on footings etc.
- Always assume a hinged end
     support for column footing for analysis unless it is supported by
     raft  and on pile cap. 
     The Common assumption of full fixity at
the column base may only be valid for columns supported on RIGID RAFT   foundations or on individual foundation pads
supported by 
      short stiff piles or by foundation walls
in Basement. Foundation pads supported on deformable soil may have considerable
rotational flexibility, resulting in column forces in the  
      bottom story quite different from those
resulting from the assumption of a rigid base. The consequences can be
unexpected column HINGES at the top of lower story 
      columns under seismic lateral forces. In
such cases the column base should be modeled by a rotational springs. (Ref:page
164-Seismic design of Reinforced concrete and 
      Masonry buildings by T.Paulay &
M.J.N.Priestley.) 
      Also refer the Reinforced concrete
Designer’s Handbook by Reynold where it is clearly mention about the column
base support.
R.C.C.WALLS:
- The minimum reinforcement for
     the RCC wall subject to BM shall be as follows:
- Vertical reinforcement:
a)    0.0012  of cross sectional area for deformed bars not
larger than 16mm in diameter and with characteristic strength 415 N/mm^2 or
greater.
b)   0.0015  of cross sectional area for other types of
bars.
c)    0.0012 of cross sectional area for
welded fabric not larger than 16mm in diameter.
Maximum
horizontal spacing for the vertical reinforcement shall neither exceed three
times the wall thickness nor 450mm.
- Horizontal reinforcement.
a)    0.0020 of cross sectional area for
deformed bars not larger than 16mm in diameter and with characteristic strength
415 N/mm^2 or greater.
b)   0.0025  of cross sectional area for other types of
bars.
c)    0.0020 of cross sectional area for
welded fabric not larger than 16mm in diameter.
Maximum
vertical l spacing for the vertical reinforcement shall neither exceed three
times the wall thickness nor 450mm.
NOTE:
The minimum reinforcement may not always be sufficient to provide adequate
resistance to effects of shrinkage and temperature.
 
No comments:
Post a Comment