RCC MEMBER DESIGN
TIPS
A.BEAMS:
OVERALL
DEPTH OF BEAMS:
SL.NO
|
MEMBER
|
SPAN/OVERALL DEPTH RATIO
|
1.
|
PLINTH BEAM
|
15 TO 18
|
2.
|
TIE BEAM
|
18 TO 20
|
3.
|
FLOOR BEAMS
|
12 TO 15
|
4.
|
GRID BEAMS
|
20 TO 30
|
1. Beam sections should be designed for:
- Moment values at the column face
& (not the value at center line as per analysis)
- Shear values at distance of
d from the column face. (not the
value at center line as per analysis)
- Moment redistribution is allowed
for static loads only.
- For beams spanning between the
columns about the weak axis, the moments at the end support shall be
reduced more and distributed and the span moments shall be increased
accordingly to account for the above reduction.
- Moment distribution shall be
done in such a way that 15% of the support moments shall be added to the
span moment without the support moments getting reduced.
- The section within the span
shall be designed for the increased span moment which will account for the
concentrated & isolated loading that may act within one span.
- Moment redistribution is not
allowed if
- moment co-efficient taken from
code table
- designed for earthquake forces
and for lateral loads.
- At least 1/3 of the +ve moment
reinforcement in SIMPLE SUPPORTS & ¼ the +ve moment reinforcement in
CONTINUOUS MEMBERS shall extend along the same face of the member into the
support, to a length equal to Ld/3. (Ld-development length)
- Use higher grade of concrete if
most of the beams are doubly reinforced. Also when Mu/bd^2 goes above 6.0.
- Try to design a minimum width
for beams so that the all beam reinforcement passes through the columns.
This is for the reason that any reinforcement outside the column will be
ineffective in resisting compression.
- Restrict the spacing of stirrups
to 8”(200mm) or ¾ of effective depth whichever is less.(for static loads)
- Whenever possible try to use
T-beam or L-beam concept so as to avoid compression reinforcement.
- Use a min. of 0.2% for
compression reinforcement to aid in controlling the deflection, creep and
other long term deflections.
- Bars of Secondary beam shall
rest on the bars of the Primary beam if the beams are of the same depth.
The kinking of bars shall be shown clearly on the drawing.
- Length of curtailment shall be
checked with the required development length.
- Keep the higher diameter bars
away from the N.A(i.e. layer nearest to the tension face) so that max.
lever arm will be available.
- Hanger bars shall be provided on
the main beam whenever heavy secondary beam rests on the main beam.(Try to
avoid the hanger bar if secondary beam has less depth than the main beam,
as there are enough cushions available).
- The detailing for the secondary
beam shall be done so that it does not induce any TORSION on the main
beam.
- For cantilever beams reinforcement at the
support shall be given a little more and the development length shall be
given 25% more.
- As a short cut, bending moment
for a beam (partially continuous or fully continuous) can be assumed as
wl^2/10 and the same reinforcement can be detailed at span and support.
This thumb rule should not be applied for simply supported beams.
B:SLAB
EFFECTIVE DEPTH:
Sl.no
|
SLAB
|
SPAN/EFFE.DEPTH
|
1.
|
One- way simply supported slab
|
30
|
2.
|
One-way continuous slabs
|
35
|
3.
|
Two-way simply supported slabs
|
38 for L/B=1.5
35 for
L/B>1.5
|
4.
|
Teo-way continuous slabs
|
40 for L/B=1.5
38 for
L/B>1.5
|
- Whenever the slab thickness is
150mm, the bar diameter shall be 10mm for normal spacing.(It can be 8mm at
very closely spaced).
- Slab thickness can be
100mm,110mm,120mm,125mm,150mm, etc.
- The maximum spacing of Main bar
shall not exceed 200mm(8”) and the distribution bars @ 250mm(10”).
- If the roof slab is supported by
load bearing wall(without any frames) a bed block of 150/200mm shall be
provided along the length of supports which will aid in resisting the
lateral forces.
- If the roof is of sheet(AC/GI)
supported by load bearing wall (without any frames) a bed block of
150/200mm shall be provided along the length of supports except at the
eaves. The bed block is provided to keep the sheets in position from WIND.
- For the roof slab provide a min.
of 0.24% of slab cross sectional
area reinforcement to take care of the temperature and other weathering
agent and for the ponding of rain water etc since it is exposed to outside
the building enclosure.
COLUMN:
- Section should be designed for
the column moment values at the beam face.
- Use higher grade of concrete
when the axial load is predominant.
- Go for a higher section
properties when the moment is predominant.
- Restrict the maximum % of reinforcement
to 3.
- Detail the reinforcement in
column in such a way that it gets maximum lever arm for the axis about
which the column moment acts.
- Position of lap shall be clearly
mentioned in the drawing according to the change in reinforcement.
Whenever there is a change in reinforcement at a junction, lap shall be
provided to that side of the junction where the reinforcement is less.
- Provide laps at mid height of
column to minimize the damage due to moments(Seismic forces).
- Avoid KICKER concrete to fix column
form work since it is the weakest link due to weak and non compacted part.
FOOTING:
- Never assume the soil bearing
capacity and at least have one trial pit to get the real site Bearing
capacity value.
- Check the Factor of Safety used
by the Geo technical engineer for finding the SBC.
- SBC can be increased depending
on the N-value and type of footing that is going to be designed. Vide
IS-1893-2000(part-I).
- Provide always PLINTH BEAMS
resting on natural ground in orthogonal directions connecting all
columns which will help in many respect like reducing the differential
settlement of foundations, reducing the moments on footings etc.
- Always assume a hinged end
support for column footing for analysis unless it is supported by
raft and on pile cap.
The Common assumption of full fixity at
the column base may only be valid for columns supported on RIGID RAFT foundations or on individual foundation pads
supported by
short stiff piles or by foundation walls
in Basement. Foundation pads supported on deformable soil may have considerable
rotational flexibility, resulting in column forces in the
bottom story quite different from those
resulting from the assumption of a rigid base. The consequences can be
unexpected column HINGES at the top of lower story
columns under seismic lateral forces. In
such cases the column base should be modeled by a rotational springs. (Ref:page
164-Seismic design of Reinforced concrete and
Masonry buildings by T.Paulay &
M.J.N.Priestley.)
Also refer the Reinforced concrete
Designer’s Handbook by Reynold where it is clearly mention about the column
base support.
R.C.C.WALLS:
- The minimum reinforcement for
the RCC wall subject to BM shall be as follows:
- Vertical reinforcement:
a) 0.0012 of cross sectional area for deformed bars not
larger than 16mm in diameter and with characteristic strength 415 N/mm^2 or
greater.
b) 0.0015 of cross sectional area for other types of
bars.
c) 0.0012 of cross sectional area for
welded fabric not larger than 16mm in diameter.
Maximum
horizontal spacing for the vertical reinforcement shall neither exceed three
times the wall thickness nor 450mm.
- Horizontal reinforcement.
a) 0.0020 of cross sectional area for
deformed bars not larger than 16mm in diameter and with characteristic strength
415 N/mm^2 or greater.
b) 0.0025 of cross sectional area for other types of
bars.
c) 0.0020 of cross sectional area for
welded fabric not larger than 16mm in diameter.
Maximum
vertical l spacing for the vertical reinforcement shall neither exceed three
times the wall thickness nor 450mm.
NOTE:
The minimum reinforcement may not always be sufficient to provide adequate
resistance to effects of shrinkage and temperature.
No comments:
Post a Comment